- 0.6 mm2 for loop lengths up to 400 metres*
- 0.8 mm2 for loop lengths up to 600 metres*
- 1.0 mm2 for loop lengths up to 800 metres*
- 1.5 mm2 for loop lengths up to 1,200 metres*
- 2.5 mm2 for loop lengths up to 2,000 metres*
- INT-RS422-P2P-D / INT-RS422-P2P-S: 1,200M
- INT-FO-P2P-D / INT-FO-P2P-S: 2,400M
- INT-TCP-IP-P2P*: Follow guidelines of cable and internet device (Ethernet Switch) manufacturer
- INT-RS422-P2P / MIX FO: 1,200M and 2,400M
*INT-TCP-IP-P2P is currently under development. The alternative is J-NET-INT-TCP/IP.
Chameleon protocol panels also support media convertors for longer distance
lengths of up to 10km.
For more information email us at techs@globalfire-equipment.com
- INT-RS422-P2P-D / INT-RS422-P2P-S: 1,200M
- INT-FO-P2P-D / INT-FO-P2P-S: 2,400M
- INT-TCP-IP-P2P*: Follow guidelines of cable and internet device (Ethernet Switch) manufacturer
- INT-RS422-P2P / MIX FO: 1,200M and 2,400M
*INT-TCP-IP-P2P is currently under development. The alternative is J-NET-INT-TCP/IP.
Chameleon protocol panels also support media convertors for longer distance
lengths of up to 10km.
For more information email us at techs@globalfire-equipment.com
The maximum battery capacity is different for each panel and is as follows:
- G-One, GEKKO, OCTO+ and NODE+: 12 A/h
- ORION and ORION PLUS panels: 7 A/h
- ORION-MINI panel: 12 A/h
- GFE-BCM-3 psu: 7 A/h
- GFE-BCM-5/10 psu: 12 A/h
- BCM-10 charger module: 40 A/h (LiFePo4)
The CHAMELEON LOOP AND BATTERY CALCULATOR software enables the calculation of the required batteries for GFE addressable systems.
- INT-RS232-DB9
- Cable interconnecting panels, DB9 connectors, RS232(DB9) to USB Convertor.
- Odyssey and Modbus compatible
- INT-RS422-P2P-S
- INT-RS485-DTLOOP
- RS232-to-RS485/422 converter from BB Electronics to be fitted at the PC
- Cable interconnecting panels and converter
- Odyssey and Modbus compatible
- INT-FO-P2P-S
- RS232-to-fibre optics converter from BB Electronics (FOSTC) to be fitted at the PC
- Fibre optic cable interconnecting panel and converter. Terminations are ST type and fibre has to be of multimode type 125/62.5 um.
- Odyssey and Modbus compatible
- INT-TCPIP-P2P (currently in development)
- Ensure the cable length does not exceed 1.5 metres
- Login to the panel with an installation or higher-level password
- Access function 8-4-1 should be set to ‘Installation Mode’
- Begin the required process (download/upload) in the CHAMELEON CONNECTOR software
- Programming mode – which allows you to configure, program and download data to the panel.
- Device data mode – which shows the addressable devices present on the detection loops.
There is also a:
- Firmware update mode – which is used for updating panels.